Application | Recommended Sizing ( microns) |
Comments |
Cooling Tower Bleed-off / Blowd | 5-55 | |
Closed loop filtration | 5-55 | |
Tower Basin Cleaning / Sweeper Jet | 5-55 | |
Cartridge replacement | 2-55 | |
Protection of Heat exchangers | 5-55 | Consult with manufacturer |
Invasive Species | 40-70 | For larva removal |
Membrane Protection | 70-300 | |
Coal Ash | 20-50 | depends on process treatment train |
Model | 3” x (3) x 6” | 3” x (4) x 6” | 3” x (5) x 6” | 3” x (6) x 6” | 3” x (7) x 6” | 3” x (8) x 6” |
General Specifications | ||||||
Max. filtration flow rate* | 240 gpm | 320 gpm | 400 gpm | 480 gpm | 560 gpm | 640 gpm |
Backwash flow rate | 100 gpm | |||||
Filter pump HP | 10 | 15 | ||||
BW booster pump HP | 5 | |||||
Filter face pipe (flange) | 6” | |||||
Flush line (flange) | 4” | |||||
Backwash water volume per cycle (gallons) |
~ 100 | ~ 133 | ~ 167 | ~ 200 | ~ 233 | ~ 267 |
Dry weight horiz / vert (lbs.) |
1,194/1,548 | 1,493/1,885 | 1,558/1,930 | 1,603/1,975 | 2,169/N/A | 2,215/N/A |
*Flow is based on 55 μ filtration degree (Green discs) at Max TSS of 35 PPM |