Application | Recommended Sizing ( microns) |
Comments |
Cooling Tower Bleed-off / Blowd | 5-55 | |
Closed loop filtration | 5-55 | |
Tower Basin Cleaning / Sweeper Jet | 5-55 | |
Cartridge replacement | 2-55 | |
Protection of Heat exchangers | 5-55 | Consult with manufacturer |
Invasive Species | 40-70 | For larva removal |
Membrane Protection | 70-300 | |
Coal Ash | 20-50 | depends on process treatment train |
Model | 4” x (4) x 10” | 4” x (5) x 10” | 4” x (6) x 12” | 4” x (7) x 12” | 4” x (8) x 12” |
General Specifications | |||||
Max. filtration flow rate* | 800 gpm | 1,000 gpm | 1,200 gpm | 1,400 gpm | 1,600 gpm |
Backwash flow rate | 250 gpm | ||||
Filter pump HP | 20 | 30 | |||
BW booster pump HP | 15 | ||||
Filter face pipe (flange) | 10” | 12” | |||
Flush line (flange) | 4” | ||||
Backwash water volume per cycle (gallons) |
~ 333 | ~ 417 | ~ 500 | ~ 583 | ~ 667 |
Dry weight horiz / vert (lbs.) |
2,913 | 3,240 | 4,158 | 4,187 | 4,377 |
*Flow is based on 55 μ filtration degree (Green discs) at Max TSS of 35 PPM |