| Application | Recommended Sizing ( microns) |
Comments |
| Cooling Tower Bleed-off / Blowd | 5-55 | |
| Closed loop filtration | 5-55 | |
| Tower Basin Cleaning / Sweeper Jet | 5-55 | |
| Cartridge replacement | 2-55 | |
| Protection of Heat exchangers | 5-55 | Consult with manufacturer |
| Invasive Species | 40-70 | For larva removal |
| Membrane Protection | 70-300 | |
| Coal Ash | 20-50 | depends on process treatment train |
| Model | 2” x (3) x 4” | 2” x (4) x 4” | 2” x (5) x 4” |
| General Specifications | |||
| Max. filtration flow rate* | 120 gpm | 160 gpm | 200 gpm |
| Backwash flow rate | 50 gpm | ||
| Filter pump HP | 7.5 | 10 | 5 |
| BW booster pump HP | N/A | 5 | |
| Filter face pipe (flange) | 4” | ||
| Flush line (flange) | 4” | ||
| Backwash water volume per cycle (gallons) |
~ 50 | ~ 67 | ~ 83 |
| Dry weight horiz / vert (lbs.) |
522/631 | 670/790 | 889/1,113 |
| *Flow is based on 55 μ filtration degree (Green discs) at Max TSS of 35 PPM | |||